Live
All Electrical Calculators
⏳ Loading calculators…

📚 Sources & Methodology

NFPA 70 (National Electrical Code) 2023 — NEC Chapter 9 Table 8 conductor resistance values, Article 210 branch circuit requirements, Article 430 motor circuit requirements, Article 647 sensitive technical power, nfpa.org2023 edition
IEEE Standard 519-2022 — Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, power quality and voltage standards, standards.ieee.org2022 edition
NEMA (National Electrical Manufacturers Association) — motor nameplate standards, Full Load Amperage (FLA) and Locked Rotor Amperage (LRA) definitions, motor starting current multipliers, nema.orgCurrent standard
Southwire Engineering — AWG resistance values, voltage drop formulas, copper vs aluminum conductor comparison, NEC ampacity tables cross-reference, southwire.comCurrent data

Voltage Drop, Ohm’s Law & Motor Starting Current — What NEC Says and What Electricians Get Wrong

Three electrical calculations account for the majority of wiring sizing decisions and inspection questions: voltage drop (is this wire big enough for this run?), Ohm’s law (what current, voltage, or resistance is in this circuit?), and motor circuit sizing (why does this breaker keep tripping?). Each has a specific error pattern. Voltage drop calculations frequently forget to double the one-way distance for the round-trip conductor path. Motor circuit breaker sizing is confused by nameplate FLA vs actual starting current. And the NEC 3% voltage drop limit is treated as a mandatory code requirement when it is an Informational Note in most sections — though it is mandatory for specific applications where people assume it is not.

Voltage Drop Calculator — The Round-Trip Distance Error and the NEC 3% Status

The voltage drop calculator computes conductor voltage loss for single-phase and three-phase circuits using NEC Chapter 9 Table 8 resistance values. Single-phase formula: VD = 2 × I × R × L ÷ 1,000. Three-phase: VD = √3 × I × R × L ÷ 1,000. The factor 2 in single-phase accounts for current flowing out through one conductor and returning through another — the circuit forms a loop and both legs carry the full current. Forgetting this factor understates voltage drop by exactly half. For a 120V, 20A circuit with 100ft run on 12 AWG copper: VD = 2 × 20 × 1.93 × 100 ÷ 1,000 = 7.72V = 6.4% — more than double the NEC 3% recommendation, requiring a wire upgrade to 8 AWG or larger.

Voltage Drop — Single Phase & Three Phase Formulas Single phase: VD (V) = 2 × I × R × L ÷ 1,000 Three phase: VD (V) = √3 × I × R × L ÷ 1,000 (1.732 factor) Percent VD = (VD ÷ Source voltage) × 100 — Example: 120V, 20A, 100ft run, 12 AWG copper (R = 1.93 Ω/1000ft) — VD = 2 × 20 × 1.93 × 100 ÷ 1,000 = 7.72V (6.4%) NEC 3% limit = 3.6V max. This circuit exceeds by 4.12V. Upsize to 8 AWG (R = 0.778 Ω/1000ft): VD = 2 × 20 × 0.778 × 100 ÷ 1,000 = 3.11V = 2.6% ✗ Common error: using 100ft instead of 200ft effective length — gives 3.86V (3.2%) on 12 AWG — looks like it passes but it does not account for round trip ✓ The factor 2 in the formula accounts for both conductors. Always enter one-way distance; the formula doubles it automatically. NEC 3% applies to the branch circuit. NEC 5% applies to feeder + branch circuit combined. Both are Informational Notes in most NEC sections — meaning recommendations, not hard requirements — except for fire pumps (NEC 695.7) and sensitive technical power (NEC 647.4(D)) where they are mandatory.

Ohm’s Law — V=IR and the Power Triangle

Ohm’s Law defines the relationship between voltage (V), current (I), and resistance (R) in a linear electrical circuit. V = I × R. From this single equation, all four electrical quantities can be derived: V = I × R, I = V ÷ R, R = V ÷ I, and P = V × I where P is power in watts. Combined power formulas: P = I² × R (useful when you know current and resistance), P = V² ÷ R (useful when you know voltage and resistance). For a 120V circuit breaker tripping at 15A: maximum load = 120 × 15 = 1,800W = 1.8 kW. For a 1,500W space heater on 120V: I = 1,500 ÷ 120 = 12.5A. This heater loads the circuit to 83% of a 15A breaker — and exceeds the 80% continuous load limit (12A max continuous on 15A circuit). It must be on a dedicated 20A circuit where continuous load = 16A maximum, leaving 3.5A of headroom.

Motor Starting Current — Why 6× FLA Is the #1 Reason Breakers Trip “For No Reason”

Every electric motor draws significantly more current during startup than during normal running operation. This Locked Rotor Amperage (LRA) is typically 6 to 8 times the nameplate Full Load Amperage (FLA). A motor with a 10A nameplate FLA draws 60–80A for the 0.5 to 3 seconds needed to reach operating speed. A standard 15A breaker sized to the motor’s running current trips instantly on startup because 60A is 4 times its rating. NEC Article 430 accounts for this by allowing motor branch circuit breakers to be sized significantly larger than the running current — up to 250% of FLA for inverse time breakers. The rule: NEC Table 430.52 is the sizing guide for motor branch circuit breakers, not the nameplate current directly.

Ohm’s Law Power Triangle & Motor Starting Current V = I × R — I = V ÷ R — R = V ÷ I P = V × I — P = I² × R — P = V² ÷ R — Motor starting current example — Motor nameplate: 120V, 10A FLA (full load amperage) Running current: 10A → circuit draws 10A in steady state Starting LRA: 10A × 6 = 60A for 0.5–3 seconds ✗ Wrong: installing 15A breaker for 10A motor — 60A starting current = 400% of breaker rating = instant trip ✓ Correct (NEC 430.52): inverse time breaker at max 250% of FLA = 25A breaker for 10A motor — holds through starting inrush Motor torque varies as the square of applied voltage. A 10% voltage drop reduces available torque by 19% (0.90² = 0.81). At 3% voltage drop on the branch circuit plus 2% on feeders, motor torque is reduced by approximately 10% at rated load, with larger impacts during starting when voltage drop is highest due to high starting current.
💡

NEC 3% voltage drop is a recommendation in most cases — but IS mandatory for these applications: The NEC 3% branch circuit voltage drop limit appears as an Informational Note (formerly Fine Print Note) in NEC 210.19(A) and 215.2(A) — meaning it is an advisory recommendation, not an enforceable code requirement in most jurisdictions under the base NEC. An inspector cannot fail an installation solely for 3.5% voltage drop in most states. However, voltage drop IS mandatory (not discretionary) in three specific NEC contexts: (1) Fire pumps — NEC 695.7: voltage at the controller line terminals shall not drop more than 15% below rated voltage during motor starting. Life safety requirement. (2) Sensitive technical power — NEC 647.4(D): maximum 1.5% voltage drop. Mandatory for broadcast, recording, and similar facilities. (3) Emergency systems — NEC 700.31: specific voltage drop limits apply. Also: California Title 24 energy code includes mandatory voltage drop requirements statewide. Always check local amendments with your AHJ.

Electrical Reference Tables — AWG Ampacity, Voltage Drop by Wire Size & Motor Starting Current

AWG Wire Size Ampacity Reference — Copper Conductors (NEC Table 310.16)

Ampacity values for copper conductors in conduit, cable, or earth at 30°C ambient, 75°C conductor temperature rating — the NEC standard column used for most residential and commercial wiring. Derate for ambient temperature above 30°C and for more than 3 current-carrying conductors in the same conduit.

AWG SizeAmpacity (75°C)Resistance (Ω/1000ft)Typical Application
14 AWG15A3.1415A branch circuits, lighting
12 AWG20A1.9320A branch circuits, kitchen, bathrooms
10 AWG30A1.2430A circuits, dryers, water heaters
8 AWG40A0.77840A circuits, ranges, EV chargers
6 AWG55A0.49150–60A circuits, large HVAC
4 AWG70A0.30870A feeders, sub-panels
2 AWG95A0.19490–100A sub-feeders
1/0 AWG125A0.122100–125A service entrance
2/0 AWG145A0.0967150A service entrance
3/0 AWG165A0.0766200A service (with 4/0)

NEC Voltage Drop Thresholds — Recommendation vs Mandatory Status

Critical distinction: Informational Notes in NEC are recommendations. Mandatory means the word “shall” is used in the code body, not in a note. Always verify local amendments with your Authority Having Jurisdiction (AHJ).

ApplicationVD LimitNEC ReferenceStatus
Branch circuits (general)3%210.19(A) Info NoteRecommendation
Feeders (general)2%215.2(A) Info NoteRecommendation
Feeders + branch combined5% totalCombined Info NotesRecommendation
Fire pump motor starting15% max at startNEC 695.7MANDATORY
Sensitive technical power1.5%NEC 647.4(D)MANDATORY
Emergency systemsVariesNEC 700.31MANDATORY
California Title 24 energy code5% maxCEC Title 24MANDATORY (CA only)
Precision equipment (best practice)1–2%Engineering standardDesign recommendation

Motor Starting Current — FLA vs LRA and NEC Breaker Sizing

Motors draw 6–8× FLA during starting. NEC Table 430.52 allows motor branch circuit breakers to be sized well above the running current to hold through starting inrush without nuisance tripping.

Motor FLAStarting LRA (6×)Max Inverse Time Breaker (250%)Why Nameplate Breaker Fails
5A30A starting12.5A breaker (use 15A)5A breaker trips at 30A: 600% of rating
10A60A starting25A breaker10A breaker trips at 60A: 600% of rating
15A90A starting37.5A (use 40A)15A breaker trips at 90A: 600% of rating
20A120A starting50A breaker20A breaker trips at 120A: 600% of rating
30A180A starting75A breaker30A breaker trips at 180A: 600% of rating
⚠️

Motor starting current is 6× FLA — the #1 cause of “breaker trips for no reason” calls: When a breaker sized to the motor nameplate trips every time the motor starts, the breaker is not defective — it is correctly responding to a 600% overload during the brief starting inrush. The solution is not a larger breaker than NEC allows or a time-delay fuse alone: it is following NEC Table 430.52 which permits inverse time breakers up to 250% of motor FLA to accommodate starting current. For a 10A FLA motor, that means up to a 25A breaker (10 × 2.5 = 25). The motor’s running overload protection (a separate overload device rated at 115–125% of FLA per NEC 430.32) protects against sustained running overloads. The branch circuit breaker size handles faults and starting current — not continuous overload protection. These are two separate protective functions with separate sizing rules.

Which Electrical Calculator to Use — A Practical Guide for Electricians, Engineers & Homeowners

For Wire Sizing and Voltage Drop

Start by determining the load current and the one-way run length. Enter both into the voltage drop calculator with your circuit voltage and wire type (copper or aluminum). Check the result against the 3% branch circuit recommendation for general wiring. If voltage drop exceeds 3%: increase wire size until it does not. Remember that both ampacity and voltage drop must be satisfied — the larger of the two required wire sizes governs. For long runs to detached garages, pumps, workshops, or EV chargers, voltage drop often controls the wire size rather than ampacity. A 50A EV charger circuit on a 100ft run will typically require 4 AWG copper to meet both ampacity (sufficient) and voltage drop (the governing factor at that length).

For Motor Circuits

Do not size motor branch circuit breakers to the nameplate FLA. Use NEC Table 430.52: for inverse time (standard) breakers, maximum size is 250% of FLA. For dual-element time-delay fuses, maximum is 175% of FLA. The running overload protection (NEC 430.32) is a separate device rated at 115–125% of FLA. For a 10A FLA motor: branch circuit breaker up to 25A, overload relay at 11.5–12.5A. Wire size is based on 125% of FLA per NEC 430.22 — 10A × 1.25 = 12.5A minimum conductor ampacity, so 14 AWG at 75°C (15A) is the minimum, but verify voltage drop from panel to motor location.

For Continuous Load Circuits

The NEC 80% continuous load rule (NEC 210.20(A)) applies to any load that operates for 3 hours or more continuously: space heaters, EV chargers on timers, commercial lighting, refrigeration compressors. Size the breaker at 125% of the continuous load and verify the circuit can sustain that current. A 1,500W space heater at 120V draws 12.5A continuously — this requires a dedicated 20A circuit (16A maximum continuous), not a shared 15A circuit. The 15A circuit would be loaded at 83% of breaker rating continuously, exceeding the 80% limit and creating sustained heat buildup in the breaker and wiring.

What Electricians and Engineers Consistently Get Wrong

Three calculation errors produce the most field problems. First: forgetting to double the one-way distance for voltage drop — entering 100ft when the round-trip conductor path is 200ft halves the calculated voltage drop and can lead to undersized wire on long runs. Second: sizing motor breakers to nameplate FLA instead of per NEC Table 430.52 — resulting in nuisance trips that are blamed on the motor, the breaker, or the load rather than the incorrect sizing. Third: treating the NEC 3% voltage drop as universally mandatory when it is a recommendation in most sections — this causes over-engineering in low-stakes circuits and missed mandatory compliance in fire pump and sensitive electronics applications where it actually is required.

Frequently Asked Questions — Electrical Calculators

VD = 2 × I × R × L ÷ 1,000. I = current (amps), R = conductor resistance (Ω/1000ft from NEC Chapter 9 Table 8), L = one-way run length (feet). The factor 2 accounts for the round-trip conductor path. Example: 20A, 100ft, 12 AWG copper (R = 1.93): VD = 2 × 20 × 1.93 × 100 ÷ 1,000 = 7.72V = 6.4% on a 120V circuit. Most common error: entering the round-trip distance instead of one-way (gives double the correct drop), or omitting the factor 2 altogether (gives half the correct drop). Always enter one-way distance and use the formula as written.
Recommendation in most cases. The NEC 3% branch circuit limit appears in Informational Notes to NEC 210.19(A) and 215.2(A). Informational Notes are not enforceable requirements under the base NEC — an inspector cannot fail an installation solely for 3.5% voltage drop in most jurisdictions. Mandatory exceptions: fire pumps (NEC 695.7) have mandatory voltage drop limits during motor starting. Sensitive technical power systems (NEC 647.4(D)) require maximum 1.5% — mandatory. Emergency systems (NEC 700.31) have mandatory limits. California Title 24 makes voltage drop mandatory statewide. Always verify local amendments with your Authority Having Jurisdiction (AHJ).
Ohm’s Law: V = I × R. Voltage (volts) = Current (amps) × Resistance (ohms). Derived forms: I = V ÷ R (current from voltage and resistance), R = V ÷ I (resistance from voltage and current). Power formulas: P = V × I, P = I² × R, P = V² ÷ R. Example: 120V circuit, 1,800W load. I = 1,800 ÷ 120 = 15A. R = 120 ÷ 15 = 8Ω. For a 60W bulb at 120V: I = 60 ÷ 120 = 0.5A, R = 120 ÷ 0.5 = 240Ω. These four forms cover any two-known-one-unknown problem in resistive DC circuits and AC resistive loads.
Electric motors draw 6–8 times their nameplate FLA during starting (Locked Rotor Amperage). A 10A FLA motor draws 60–80A for 0.5–3 seconds at startup. A 10A or 15A breaker trips immediately because 60A is 400–600% of the breaker rating. Solution: per NEC Table 430.52, inverse time (standard) breakers can be sized up to 250% of motor FLA. For a 10A motor: 10 × 2.5 = 25A breaker maximum. The 25A breaker holds through the starting inrush. The running overload protection (a separate overload relay at 115–125% of FLA) handles sustained overloads — a completely separate device and sizing rule from the breaker.
NEC 210.20(A) requires overcurrent devices (breakers/fuses) to be rated at 125% of continuous loads. A continuous load operates for 3 hours or more. 125% inverse = 80% loading limit. A 20A breaker: maximum 16A continuous (20 × 0.80). A 15A breaker: maximum 12A continuous. A 1,500W heater at 120V draws 12.5A — exceeds the 12A limit on a 15A breaker. Must use a dedicated 20A circuit where 12.5A is 78% of the 16A continuous limit. This rule prevents sustained heat buildup in overcurrent devices and wiring, which degrades insulation and causes long-term reliability problems.
Two limits: ampacity and voltage drop. Both must be satisfied; use the larger wire. Ampacity (NEC Table 310.16, 75°C copper in conduit): 14 AWG = 15A, 12 AWG = 20A, 10 AWG = 30A, 8 AWG = 40A, 6 AWG = 55A. Voltage drop calculation may require a larger wire on long runs. For a 30A circuit with 200ft run: ampacity requires 10 AWG, but voltage drop at 30A on 200ft of 10 AWG = 2 × 30 × 1.24 × 200 ÷ 1,000 = 14.88V = 12.4% on 120V — far exceeding 3%. Upsize to 4 AWG or consider 240V to cut the percentage in half. Always calculate both limits.
Single-phase VD = 2 × I × R × L ÷ 1,000 (factor 2 for two conductors). Three-phase VD = √3 × I × R × L ÷ 1,000 (factor 1.732 for three-conductor system). For the same current and wire, three-phase has lower voltage drop than single-phase by a factor of 1.732 ÷ 2 = 0.866 — about 13% less drop. Three-phase power also delivers more power per ampere: P = 1.732 × V × I × PF vs P = V × I × PF for single-phase. This is why long runs and high-power equipment are typically three-phase: better efficiency at lower voltage drop per ampere of current.
Aluminum expands and contracts more than copper with temperature cycles, causing connections to loosen over time and develop resistance. Loose resistance at a connection generates heat, which can start fires. Required: connectors rated AL/CU (aluminum and copper both acceptable) or AL only. Standard copper-only connectors must not be used with aluminum wire. Also required: anti-oxidant compound at all aluminum terminations because aluminum oxidizes rapidly and aluminum oxide has high resistance. Two AWG sizes larger than copper is needed for equivalent current capacity (aluminum has 61% the conductivity of copper). Standard for service entrance and large feeders; avoid for residential branch circuits.
NEC Table 310.16 ampacity assumes: max 3 current-carrying conductors in a conduit, 30°C (86°F) ambient, 75°C conductor rating. When conditions differ, derate: 4–6 conductors in conduit = 80% of table value. 7–9 conductors = 70%. 10–20 conductors = 50%. High ambient temperature uses correction factors from NEC Table 310.15(B)(1). In a 45°C attic with 5 conductors bundled together: temperature correction × conductor bundle correction = 87% × 80% = 69.6% of table ampacity. A 12 AWG wire rated 20A at table value carries only 13.9A in these conditions. Must upsize accordingly.
Three-phase power: P = √3 × V × I × PF = 1.732 × V × I × PF. Three-phase current: I = P ÷ (1.732 × V × PF). For a 480V, 30 kW motor at 0.85 PF: I = 30,000 ÷ (1.732 × 480 × 0.85) = 30,000 ÷ 707 = 42.4A. Three-phase delivers the same power as single-phase with 42% less current (1 ÷ 1.732 = 0.577 — wait, that is at the same voltage). Comparing 240V single-phase at 42.4A: P = 240 × 42.4 × 0.85 = 8.65 kW — far less than 30 kW. Three-phase delivers substantially more power for the same conductor size and current.
The Beer-Lambert Law: A = ε × c × l, where A = absorbance (dimensionless), ε = molar absorptivity (L/mol·cm), c = concentration (mol/L), l = path length (cm). Used in spectrophotometry to determine the concentration of a substance from its light absorption. Rearranged for concentration: c = A ÷ (ε × l). Also written as A = log(I&sub0; ÷ I) where I&sub0; is incident light intensity and I is transmitted intensity. This law appears in analytical chemistry, environmental monitoring, and biomedical applications. The Beer-Lambert Law calculator solves for any of the four variables given the other three.
No. Every electrical calculation runs entirely in your browser. Your voltage, current, wire lengths, and all other inputs never leave your device. Nothing is logged or stored. Electrical calculator results are for planning and educational purposes only. All electrical installations must comply with the currently adopted NEC edition and applicable local amendments. Have designs reviewed by a licensed electrician or engineer before installation. Calculations do not substitute for inspection, permitting, or professional engineering review.

Popular Calculators

Most used tools across all 14 categories

Related Calculator Categories

Missing an Electrical Calculator?

Can’t find the tool you need? Tell us — we build new electrical calculators every week, prioritising the most-requested tools for electricians, engineers, and contractors.